Heater operation and fan run-on
What happens, in order
- Once the heater is installed and powered, the ventilator LCD shows a thermometer icon.
- At intake air 39°F to 54°F (4 to 12°C) the heater runs stage 1 and the LCD shows 1.
- At intake air 33°F to 39°F (1 to 4°C) the heater runs stage 2 and the LCD shows 1 2.
- When the ventilator controller turns the heater off, the blower keeps running to deliver residual heat to the living space.
Timings and thresholds
| Item | Value |
|---|---|
| Blower run-on after heating element turns off | 30 seconds |
Codes you may see during this
Applies to: Daikin One Powered Ventilator with heater accessory
Models
DQ-P-70-AH-HDQ-P-16-100
More Daikin general sequences
- Power-on and start-up · Startup
- Optional heater accessory staging (DQ-P-70-AH-H) · Heating
- Humidifying filter drying after humidifying stops · Standby/shutdown
- Shutdown for prolonged non-use · Standby/shutdown
- Stopping operation · Standby/shutdown
- AUTO operation switching and monitoring mode · Other
- Damper open and close sequence with ventilator · Other
- Energy Savings mode sampling cycle (out-of-limit intake air) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: IO-DPVH installation and operation manual, p. 4. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.