Heater operation and fan run-on

Daikin One Powered Ventilator

What happens, in order

  1. Once the heater is installed and powered, the ventilator LCD shows a thermometer icon.
  2. At intake air 39°F to 54°F (4 to 12°C) the heater runs stage 1 and the LCD shows 1.
  3. At intake air 33°F to 39°F (1 to 4°C) the heater runs stage 2 and the LCD shows 1 2.
  4. When the ventilator controller turns the heater off, the blower keeps running to deliver residual heat to the living space.

Timings and thresholds

ItemValue
Blower run-on after heating element turns off30 seconds

Codes you may see during this

1 1 2

Applies to: Daikin One Powered Ventilator with heater accessory

Models

DQ-P-70-AH-HDQ-P-16-100

More Daikin general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: IO-DPVH installation and operation manual, p. 4. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.