Optional heater accessory staging (DQ-P-70-AH-H)

Daikin One Powered Ventilator

What happens, in order

  1. With the heater installed and powered, the LCD shows a thermometer icon.
  2. Intake air from 39 F to 54 F (4 C to 12 C): heater runs Stage 1 and the display shows 1.
  3. Intake air from 33 F to 39 F (1 C to 4 C): heater runs Stage 2 and the display shows 1 2.

Codes you may see during this

1 1 2

Applies to: DQ-P-16-100

Models

DQ-P-16-100

More Daikin general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: IO-DPV installation manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.