Daikin · General · Heating
Optional heater accessory staging (DQ-P-70-AH-H)
What happens, in order
- With the heater installed and powered, the LCD shows a thermometer icon.
- Intake air from 39 F to 54 F (4 C to 12 C): heater runs Stage 1 and the display shows 1.
- Intake air from 33 F to 39 F (1 C to 4 C): heater runs Stage 2 and the display shows 1 2.
Codes you may see during this
Applies to: DQ-P-16-100
Models
DQ-P-16-100
More Daikin general sequences
- Power-on and start-up · Startup
- Heater operation and fan run-on · Heating
- Humidifying filter drying after humidifying stops · Standby/shutdown
- Shutdown for prolonged non-use · Standby/shutdown
- Stopping operation · Standby/shutdown
- AUTO operation switching and monitoring mode · Other
- Damper open and close sequence with ventilator · Other
- Energy Savings mode sampling cycle (out-of-limit intake air) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: IO-DPV installation manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.