Humidifying filter drying after humidifying stops
What happens, in order
- Unit runs humidifying operation in AUTO, MODE, or humidifying and air purifying operation.
- When the unit is stopped after humidifying, the humidifying filter drying operation starts automatically if it is set to ON.
- The drying run dries the humidifying filters so they are not left semi-damp.
- If the setting is OFF, the unit does not run the drying operation.
Applies to: Humidifying filter drying setting ON
Models
MCKB70YSAU
More Daikin general sequences
- Power-on and start-up · Startup
- Heater operation and fan run-on · Heating
- Optional heater accessory staging (DQ-P-70-AH-H) · Heating
- Shutdown for prolonged non-use · Standby/shutdown
- Stopping operation · Standby/shutdown
- AUTO operation switching and monitoring mode · Other
- Damper open and close sequence with ventilator · Other
- Energy Savings mode sampling cycle (out-of-limit intake air) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin MCKB70YSAU installation & operation manual, p. 23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.