NHW700 freeze protection not working

Navien NHW700

What is going on

Freeze protection runs the pump and fires the burner based on the outlet sensor.

Likely causes

  • Outlet and inlet sensors both failed
  • No power to the heater

Check in this order

  1. It turns on when the water stays below the set point for 20 seconds and off when it is 4 C above it for 20 seconds.
  2. Set point 1 C on universal/indoor models, 0 C on exterior models.
  3. If the outlet sensor fails it uses the inlet sensor. If both fail there is no freeze protection: fix any E407/E421/E441 first.
  4. It needs power and does not run during normal firing.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 6.4 p.87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.