Navien · Tankless water heater troubleshooting

E012 flame loss on NHW700

Navien NHW700

What is going on

The flame went out while running. The heater shuts the gas, tries again and counts. After 20 flame losses in a row it shows E012 and locks out (manual reset).

Likely causes

  • Low gas pressure, mostly when other gas appliances run
  • Gas meter or gas line too small, crushed packing or tape in a fitting
  • Wrong DIP switch setting or low-stage gas pressure set wrong
  • Dirty flame rod
  • Cracked or shifted burner plate
  • Blocked manifold (flame loss on stage 2)
  • Gas valve, APS, ground or power problem
  • PCB fault

Check in this order

  1. Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
  2. Check inlet gas pressure static and while the heater and other appliances fire. Check the meter size and the gas connector.
  3. Check the DIP switches and the low-stage gas pressure adjustment.
  4. Clean or replace the flame rod.
  5. Look at the burner plate for cracks or shifting and check the flame rod gap.
  6. Loses flame on stage 2 check the manifold for blockage.
  7. Check the gas valve, APS, ground wire and supply voltage (97-138 V AC).
  8. Still there replace the PCB.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.3 p.98, 7.2 p.90, 5.5 p.75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.