Navien · Tankless water heater troubleshooting
E110 air pressure fault on NHW700
What is going on
The fan is spinning faster than normal but the APS reads less pressure than it should. Usually a blocked air or exhaust path.
Likely causes
- Blocked or crushed vent or air intake
- Rain water collected in a vertical intake pipe
- Exhaust being drawn back into the intake
- Debris or soot on the heat exchanger
- Condensate in the exhaust duct or APS hose
- Broken or blocked APS hose, bad APS
- Old PCB software
Check in this order
- Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
- Check the exhaust and intake outside for blockage, damage or nests. Clear them and reset.
- Check for water in the intake pipe, condensate in the exhaust duct and inside the APS and its hoses.
- Check the exhaust is not being pulled back into the intake.
- If it comes and goes, run the heater at fixed min and max (DIP 1-1 and 1-2) and compare fan speed to normal. Higher than normal points to a blockage or APS hose problem.
- Check the APS hose and the APS voltages.
- Check the heat exchanger for debris or soot.
- Manual says to fit the latest PCB version if it keeps happening. Put DIP 1-1/1-2 back to OFF when done.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.8 p.104, 5.11 p.81, 5.12.1 p.82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.