Navien · Tankless water heater troubleshooting
Cascade, panel and air handler codes on NHW700 (E438, E736, E740, E782, E785)
What is going on
E438 = air handler (AHU) pump, E736 = cascade communication, E740 = AHU outdoor thermistor (sub 1 open, 2 short), E782 = main panel communication, E785 = AHU direct water flow switch. All alarms except E438 (manual reset).
Likely causes
- External pump not running
- Cascade wiring fault
- Outdoor sensor wiring or outdoor reset not set up
- Front panel or panel cable fault
- Flow switch wiring
- PCB fault
Check in this order
- Power off before unplugging connectors or measuring resistance.
- E438 check the external circulation pump runs.
- E736 check the cascade wiring between units, then the PCB.
- E740 check the outdoor reset curve is set up, then the outdoor sensor wiring.
- E782 check the panel cable at both ends, then the panel, then the PCB.
- E785 check the flow switch wiring, then the PCB.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.1 p.88-89, 7.2 p.91. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.