Navien · Tankless water heater troubleshooting

E016 / E046 overheating and high limit switch on NHW700

Navien NHW700

What is going on

E016: the heat exchanger high limit opened while firing (manual reset). E046: the high limit signal stayed on for over 15 seconds, or was seen before firing or during post-purge (auto reset when the signal clears). The high limit is there to stop the burner if the heat exchanger goes over 96 C (205 F).

Likely causes

  • Scale in the heat exchanger
  • Wrong capacity DIP switch setting
  • High-stage gas pressure set too high
  • Hot water thermistor reading low
  • Bad high limit switch or open thermal fuse
  • Loose wiring between high limit, thermal fuse and PCB
  • PCB fault

Check in this order

  1. Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
  2. E016 turn the heater off for at least 30 minutes, then restart. Clean the inlet filter and check all valves are open.
  3. Check the capacity DIP switches (DIP 2) match the model.
  4. Check the high-stage gas pressure setting.
  5. Check the hot water thermistor resistance. A sensor reading low makes the heater overfire.
  6. Let the heat exchanger outlet cool below 96 C (205 F). Unplug the high limit and check continuity across its pins. No continuity: replace it.
  7. Unplug the thermal fuse and measure it 0.1-0.3 ohm is good, OL means open, replace it.
  8. Check the wiring from high limit and thermal fuse to the PCB.
  9. Listen for boiling and look for cracks or soot on the heat exchanger. Heavy scale: descale or replace.
  10. The table also lists E031 (burner overheat): check the burner fuse.
  11. Still there replace the PCB.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.4 p.99, 7.3.5 p.100, 7.2 p.90, 5.1 p.70, 5.6 p.76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.