Navien · Tankless water heater troubleshooting

NHW700 error history, sub codes and resets

Navien NHW700

What is going on

How to read the last 10 errors with their sub code and how reset works.

Likely causes

  • Lock-out errors need a manual reset or power off/on
  • Auto reset errors clear when the problem clears

Check in this order

  1. From normal or error display, hold the Information button 2 seconds. Error 0 is the newest; Up/Down scroll through 10.
  2. Press Information to switch between hours since the previous error (max 9999) and the sub code.
  3. Hold Reset 5 seconds in history mode to clear it (CLR shows). Press Reset once to go back.
  4. Diagnostics button once shows the service information list.
  5. In lock-out the heater only restarts after reset or power off/on. After an error clears the fan stops for 10 seconds.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 4.11 p.64, 4.12 p.65, 6.3 p.87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.