Navien · Tankless water heater troubleshooting
NaviCirc: lukewarm water when the cold tap is first opened
What is going on
With a NaviCirc there is no return line, so the cold line is used as the return. A little warm water in the cold line is expected. The valve closes the hot-to-cold crossover at about 95 F (35 C).
Likely causes
- Normal operation of the crossover valve: cold line carries recirculated water
- Possible valve problem if it does not stop at about 95 F (see section 3 of the manual)
Check in this order
- Tell the customer that lukewarm water for a moment when they first open the cold tap is normal with this setup.
- The valve shuts the crossover at about 95 F (35 C). Valve flow range is 0.53-1.06 GPM (2-4 L/min).
- Check the heater set temperature and recirc mode are correct (see the 'far faucet slow' guide).
- If hot water keeps coming out of the cold tap, check the manual's troubleshooting table, section 3 p.86, before replacing the valve.
Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.5-6, 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.