Navien · Tankless water heater troubleshooting

NaviCirc: lukewarm water when the cold tap is first opened

Navien NaviCirc

What is going on

With a NaviCirc there is no return line, so the cold line is used as the return. A little warm water in the cold line is expected. The valve closes the hot-to-cold crossover at about 95 F (35 C).

Likely causes

  • Normal operation of the crossover valve: cold line carries recirculated water
  • Possible valve problem if it does not stop at about 95 F (see section 3 of the manual)

Check in this order

  1. Tell the customer that lukewarm water for a moment when they first open the cold tap is normal with this setup.
  2. The valve shuts the crossover at about 95 F (35 C). Valve flow range is 0.53-1.06 GPM (2-4 L/min).
  3. Check the heater set temperature and recirc mode are correct (see the 'far faucet slow' guide).
  4. If hot water keeps coming out of the cold tap, check the manual's troubleshooting table, section 3 p.86, before replacing the valve.

Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.5-6, 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.