Navien · Tankless water heater troubleshooting

NaviCirc: far faucet still slow to get hot water

Navien NaviCirc

What is going on

The NaviCirc sits under the faucet farthest from the heater and lets hot water cross into the cold line so the pump can keep the hot line warm. If hot water still takes long at the tap, the heater is usually not set for external recirculation, the pump is wrong or not wired, or the valve is in the wrong spot.

Likely causes

  • NaviCirc installed at a faucet close to the heater instead of the farthest one
  • Heater or boiler not set for external recirculation (DIP switch, parameter or menu)
  • 2-way valve inside the NPE heater not set to EXT
  • External pump not wired to TB1, or pump too small for the loop
  • Recirculation pipe run longer than the limit for its size
  • Air left in the lines after install

Check in this order

  1. Safety turn off power before you open the front cover or touch the PCB or pump wiring.
  2. Check where the NaviCirc is. It must be at the faucet farthest from the heater. Close to the heater, the far faucets stay slow.
  3. Make sure the hot and cold shutoff valves under the sink are open.
  4. NPE-A front panel DIP SW2 must be ON (external recirc). Turn the heater off, enter the R&D menu (Up x3, Down x3, Up x4), go to 2.PAR and set P17 (thermal bypass valve) to ON. Set the internal 2-way valve to EXT. A cold-line branch must go to the RECIRCULATION RETURN connection.
  5. NPE-A2/S2 set the 2-way valve to EXT, then Menu > 1. Recirculation Setting > 2. External Recirculation. On an A2 using an external pump, answer YES to 'external pump connected'.
  6. NPN the external pump wire must be on TB1 and the recirc switches on the 10-switch DIP (SW1) set for the mode you want. Pump timers are P12 (cycle time), P14 (sampling) and P15 (off differential) in the R&D menu.
  7. NCB-H / NFC-H Menu > 3. DHW Operation > DHW Recirculation > External. Intelligent or Weekly works best with the NaviCirc. External recirc is not available on cascade systems. For Aquastat mode the aquastat goes on CNC6.
  8. Pump size it for 2-4 GPM through the heater at about 15-23 ft of head. The Navien pump wire (GXXX001319) handles 150 W / 1.5 A max; use a relay for a bigger pump. Combi boilers: Taco 008-BC6 or Grundfos 15-42 BUC7 or equal, recirc pump output max 2.5 A.
  9. Check the loop length max 100 ft equivalent of 1/2 in copper or 400 ft of 3/4 in. Longer runs need a bigger pump.
  10. Purge the air again (open hot and cold faucets) and retest. Air in the lines can stop the valve working and can damage the pump.
  11. Still slow see the troubleshooting table in section 3 (p.86) of the manual.

Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.7, 14-17, 22-24, 26, 42-49, 54-56, 62-64, 69-71, 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.