Navien · Tankless water heater troubleshooting

HotButton push button does not start recirculation (NaviCirc system)

Navien NaviCirc

What is going on

The HotButton starts a recirculation run only when someone pushes a button. NPE-A2/S2 heaters have the HotButton controller built in; the buttons, wall plates and temperature sensor are bought separately.

Likely causes

  • HotButton turned off on its DIP switch
  • Heater or boiler not set for recirculation / HotButton mode
  • Wiring too long, too thin, or on the wrong terminals
  • Metal plate still on SENSOR I when a temperature sensor was added

Check in this order

  1. Safety turn off power to the heater before you work on the controller wiring.
  2. HotButton DIP SW1 OFF = HotButton enabled (default). SW2: OFF = energy saver on (default); the energy saver limits run time and may be required by local code.
  3. The HotButton only works when the heater is set up for DHW recirculation. Other recirculation functions are disabled when it is used.
  4. NCB-H / NFC-H DHW Recirculation must be External > HotButton (Manual).
  5. NPE-A with a HotButton, P12 (pump cycle time) can be set to 5 minutes max.
  6. Wired buttons go to SIGNAL 2 (not polarity sensitive). SIGNAL 1 (12 V / GND / 5 V) is for wireless buttons or a motion sensor. Several buttons can share the same terminals or a common branch.
  7. Up to 10 buttons per controller. Use UTP cable or wire heavier than AWG 24, total cable no more than 328 ft (100 m). Use spade connectors.
  8. Temperature sensor remove the metal plate from SENSOR I before connecting it. On NPN, insulate the sensor; its wire can be extended up to 100 ft with 22 AWG.
  9. Recirculation can also be started from the NaviLink app if the NaviLink WiFi kit is installed.

Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.16, 32-37, 52-53, 55-56, 65-68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.