Navien · Tankless water heater troubleshooting
HotButton push button does not start recirculation (NaviCirc system)
What is going on
The HotButton starts a recirculation run only when someone pushes a button. NPE-A2/S2 heaters have the HotButton controller built in; the buttons, wall plates and temperature sensor are bought separately.
Likely causes
- HotButton turned off on its DIP switch
- Heater or boiler not set for recirculation / HotButton mode
- Wiring too long, too thin, or on the wrong terminals
- Metal plate still on SENSOR I when a temperature sensor was added
Check in this order
- Safety turn off power to the heater before you work on the controller wiring.
- HotButton DIP SW1 OFF = HotButton enabled (default). SW2: OFF = energy saver on (default); the energy saver limits run time and may be required by local code.
- The HotButton only works when the heater is set up for DHW recirculation. Other recirculation functions are disabled when it is used.
- NCB-H / NFC-H DHW Recirculation must be External > HotButton (Manual).
- NPE-A with a HotButton, P12 (pump cycle time) can be set to 5 minutes max.
- Wired buttons go to SIGNAL 2 (not polarity sensitive). SIGNAL 1 (12 V / GND / 5 V) is for wireless buttons or a motion sensor. Several buttons can share the same terminals or a common branch.
- Up to 10 buttons per controller. Use UTP cable or wire heavier than AWG 24, total cable no more than 328 ft (100 m). Use spade connectors.
- Temperature sensor remove the metal plate from SENSOR I before connecting it. On NPN, insulate the sensor; its wire can be extended up to 100 ft with 22 AWG.
- Recirculation can also be started from the NaviLink app if the NaviLink WiFi kit is installed.
Applies to: NaviCirc recirculation valve (PFFW-SXX-001) on Navien NPE-A/A2/S2, NPN water heaters and NCB-H/NFC-H combi boilers
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NaviCirc Installation and Operation Manual (navicirc-installation-and-operation-manual-en.pdf), p.16, 32-37, 52-53, 55-56, 65-68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.