E762 vent (flue) dislocation on NHW700

Navien NHW700

What is going on

The flue dislocation switch on the vent collar was open for more than 10 seconds. Universal/indoor models. Auto reset.

Likely causes

  • Vent pipe not fully seated or wrong size
  • Bent or misaligned vent pipe
  • Switch wire loose
  • Failed switch

Check in this order

  1. Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
  2. Check the vent pipe is the right size and pushed all the way in.
  3. Check the switch wiring (blue-blue, normally closed).
  4. Check the switch opens and closes properly. Replace it if not.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.17 p.111, 7.2 p.91, 3.5 p.45, 5.5 p.74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.