Navien · Tankless water heater troubleshooting
E762 vent (flue) dislocation on NHW700
What is going on
The flue dislocation switch on the vent collar was open for more than 10 seconds. Universal/indoor models. Auto reset.
Likely causes
- Vent pipe not fully seated or wrong size
- Bent or misaligned vent pipe
- Switch wire loose
- Failed switch
Check in this order
- Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
- Check the vent pipe is the right size and pushed all the way in.
- Check the switch wiring (blue-blue, normally closed).
- Check the switch opens and closes properly. Replace it if not.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.17 p.111, 7.2 p.91, 3.5 p.45, 5.5 p.74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.