E515 / E594 / E615 board and gas valve sub codes on NHW700
What is going on
E515 sub codes: 1 and 2 = watchdog SSR (check the APS), 3 = main gas valve feedback, 5, 6, 7, 15 = manifold valves #1, #2, #3, #4, 10 = monitoring device (PCB). E594 = EEPROM (alarm). E615 sub 1-17 = input and memory (PCB).
Likely causes
- APS problem (sub 1, 2)
- Gas valve wire or coil (sub 3)
- Manifold solenoid wire or coil (sub 5, 6, 7, 15)
- PCB fault (sub 10, E594, E615)
Check in this order
- Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
- Read the sub code in the error history first.
- Sub 1 or 2 check the APS and its hoses.
- Sub 3 reseat the main gas valve plug and measure the coil. Out of range: replace the gas valve.
- Sub 5, 6, 7 or 15 reseat that manifold solenoid plug and measure its coil. Out of range: replace the manifold.
- Coil resistance values are on p.110-111. The text export did not show which value goes with which coil: read them off the page.
- Sub 10, E594, E615 cycle power. Comes back: replace the PCB.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.1 p.89, 7.2 p.91, 7.3.15 p.110-111. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.