Trane · General troubleshooting

XR724 thermostat screen is blank

Trane XR724

What is going on

The XR724 has no power. It runs on 24 VAC from the equipment, so it needs both R and C wired. No C wire = dead screen.

Likely causes

  • No 24 VAC between R and C at the thermostat
  • Transformer not putting out 24 VAC
  • Broken, shorted or loose thermostat wire

Check in this order

  1. Check that the furnace or air handler has power.
  2. At the thermostat sub-base, measure R to C. You should see about 24 VAC.
  3. No voltage there measure R to C at the equipment board. If it is good at the board, the wire run is open; check each conductor end to end.
  4. No voltage at the board check the transformer output. A shorted thermostat wire can also kill the 24 V, so check the wire run too.
  5. Make sure a C wire is actually connected at both ends. The XR724 will not run without it.

Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.