Trane · General troubleshooting
No cooling, XR724 not calling
What is going on
The XR724 does not start cooling. Check the control settings and timers first, then the equipment.
Likely causes
- System mode not on Cool or Auto, or cool setpoint set too high
- Cooling delta On set too high
- Minimum off time (compressor protection) still counting down
- Problem in the cooling equipment itself
Check in this order
- Check the mode is Cool or Auto and the setpoint is below room temperature.
- Check the cooling delta On. A large value means the room must warm up a lot before it calls.
- Wait out the minimum off time. If the customer finds it too long, change Control Response in Installer Settings > Comfort Settings.
- To split thermostat from equipment, use Menu > Test Mode > Cooling. It energizes Y1 or Y2 with O and G (BK too on a variable speed indoor unit) for 30 minutes.
- If the equipment does not run in Test Mode, the problem is in the wiring or the equipment. Go to the outdoor and indoor unit.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Test Mode p.8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.