Trane · General troubleshooting

XR724 fan set to On but blower not running

Trane XR724

What is going on

Fan mode is On but the blower stays off.

Likely causes

  • Smart Continuous Fan (SCF) is on and indoor RH is above the cooling RH target, so the control stops the fan to avoid putting moisture back in the air (SCF shows on the fan mode button)
  • Equipment problem

Check in this order

  1. Look for SCF on the fan mode button. If it is there and RH is high, this is normal.
  2. If the customer wants the fan running, turn SCF off or raise the cooling RH target.
  3. No SCF run Test Mode > Blower. If the blower still does not start, check the indoor unit.

Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.