Trane · General troubleshooting
Room goes past setpoint in cooling (XR724)
What is going on
The house cools below the cool setpoint before the system shuts off. Usually this is a setting, not a fault.
Likely causes
- Cooling delta Off is set to a negative number
- Cooling overshoot is on and indoor RH is above the cooling RH target, so the control keeps cooling to dry the house
- Minimum compressor on time has not run out yet
Check in this order
- Check indoor RH against the cooling RH target. If RH is higher, the overshoot is doing its job.
- If the customer does not want it turn cooling overshoot off, or raise the cooling RH target.
- Check the cooling delta Off. Set it to 0 if they do not want the room to go below setpoint.
- If it is the minimum on time, change Control Response under Installer Settings > Comfort Settings (Normal, Less Aggressive, More Aggressive).
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Control Response Profiles p.9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.