Trane · General troubleshooting

No heat, XR724 not calling

Trane XR724

What is going on

The XR724 does not start heating. Check the control settings and timers first, then the equipment.

Likely causes

  • System mode not on Heat or Auto, or heat setpoint set too low
  • Heating delta On set too high
  • Minimum off time still counting down
  • Problem in the heating equipment itself

Check in this order

  1. Check the mode is Heat or Auto (or EM Heat on a heat pump) and the setpoint is above room temperature.
  2. Check the heating delta On setting.
  3. Wait out the minimum off time. If it bothers the customer, change Control Response in Installer Settings > Comfort Settings.
  4. Use Menu > Test Mode > Indoor Heating (energizes W1 or W2, plus G on electric heat) or Comp Heating (Y1 or Y2 with G, BK on VS indoor units). Test Mode stays on for 30 minutes.
  5. Equipment does not run in Test Mode check the wiring and the furnace / heat pump. Gas appliances: gas-qualified tech only.

Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Test Mode p.8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.