Trane · General troubleshooting
XR724 shows the wrong room temperature
What is going on
Room temperature on the XR724 does not match a good thermometer.
Likely causes
- Sensor needs a calibration offset
- Control was powered up less than an hour ago and is still warming up
- Heat from the touchscreen trapped in the case
- Supply air, sun, a lamp or another heat source hitting the control
Check in this order
- After any power cycle, wait at least 1 hour before you judge or calibrate the reading.
- Look for drafts or heat sources near the control (supply register, sun, TV, lamp, outside wall). Move the control or redirect the air if needed.
- Calibrate the indoor sensor Menu > Calibrate Sensors > Sensor Cal. Range is +/- 7 degrees, default 0 (1 degree F = 2 degrees C on this setting).
- If a remote or outdoor sensor is used, those have their own offset (Remote Sensor Cal, ODT Sensor Cal), same +/- 7 range.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Calibrate Sensors p.5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.