XR724 shows the wrong humidity
What is going on
Indoor RH on the XR724 does not match a known good hygrometer.
Likely causes
- Humidity sensor needs a calibration offset
Check in this order
- Compare with a hygrometer you trust, placed next to the control for a while.
- Set the offset in Menu > Calibrate Sensors > RH Cal. Range is +/- 7 %, default 0 %.
- Remember the humidifier / dehumidify and overshoot functions work from this reading, so fix it before you adjust humidity targets.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Calibrate Sensors p.5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.