All brands · Furnace troubleshooting
Too little / too much air
What is going on
If rooms get too little air or too much, the first thing to look at is the total external static pressure the blower is working against. The blower table for your furnace tells you what airflow to expect at a given ESP, so a bad number there explains most complaints. Good news is you can work it out with a manometer and a little arithmetic.
Likely causes
- ESP too high or too low compared with the blower table for the furnace
Check in this order
- Measure the ESP and compute the available static pressure, ASP = ESP minus DPL
- Find the friction rate (FR) the duct has to work with, then resize or reduce fittings if the duct is the problem
- Check cfm per ton
- Use the 1.08 × cfm × ΔT check against rated furnace output
- Adjust blower speed per the manual and remeasure
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.