Can't pull oil (distance/lift)

What is going on

Every fuel pump has a limit on how far and how high it can pull oil. When the tank sits too far away or too far below the burner, the pump starves and cavitates. Stay within the vacuum rating on the pump.

Likely causes

  • Single-stage pump has a lower maximum vacuum than a two-stage pump, check each pump's rated inches of mercury in the manual
  • Lift or run length too great for the pump
  • Undersized tubing or a restricted line adds to the vacuum

Check in this order

  1. Fit a vacuum gauge on the suction side and read the vacuum with the burner running
  2. Compare the reading to the pump rating in the manual
  3. Check for a clogged filter or kinked line before blaming distance
  4. Use a two-stage pump if the single-stage is at its limit
  5. Beyond that, install a booster pump and reservoir
  6. Use bigger tubing if the run is long

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.