CO in flue / poor combustion numbers
What is going on
Carbon monoxide in the flue or poor combustion numbers on the analyzer. Read the pattern. Low CO2 with high O2 and CO means excess air is too high or manifold pressure is low. High CO2 with low O2 and CO means the burner is short of air or manifold pressure is high. Don't leave it running until you know why.
Likely causes
- Excess air too high, or manifold pressure low
- Air shortage, or manifold pressure high
- Dirty heat exchanger, restricted vent, or blocked combustion air
Check in this order
- Verify manifold pressure against the rating plate, about 3.5 in. w.c. for natural gas or 10.5 for LP
- Check the combustion air supply and openings
- Inspect the vent and flue passages for blockage
- Inspect the heat exchanger for cracks or soot
- Re-run the analyzer after each adjustment
- Gas or combustion adjustments belong to a licensed tech, and shut the furnace down if CO stays high
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.