Blower cycles on and off

What is going on

On an electric furnace, a blower that keeps starting and stopping is usually the thermostat or the high limit, not the motor. If the elements cycle along with the blower, I look at the thermostat anticipator first. If the limit is opening and closing, the airflow is the real story.

Likely causes

  • Thermostat short cycling, with the anticipator set too high
  • High limit opening and closing
  • Wrong low voltage at the control circuit
  • Blower motor overload cycling on its thermal protector

Check in this order

  1. Watch whether the elements and blower cycle together, which points at the thermostat
  2. Check the anticipator setting against the heating circuit current
  3. Meter the 24 volt control circuit at the transformer and at the thermostat
  4. Check the filter, registers and ducts for airflow restrictions that trip the limit
  5. Touch-test the blower motor after a few cycles; if it is too hot to hold, it is tripping on overload
  6. Measure motor amps and compare to the nameplate

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.