All brands · Furnace troubleshooting
Starts but locks out — no oil at nozzle
What is going on
Most times I get called for this one, the oil never makes it to the nozzle, so the burner itself is fine. The motor starts, the control waits out its safety time, and it locks out because there is no flame to prove. Nine times out of ten it is an empty tank, a plugged filter or a clogged nozzle, so I start at the tank and work toward the burner.
Likely causes
- Empty tank, closed tank shutoff, or a tank vent that is closed or blocked
- Clogged strainers: tank filter, pump screen or nozzle strainer
- Air leak in the suction line, or a loose fitting letting the pump lose prime
- Dead fuel unit, pump regulator stuck open, or pressure too low to atomize the oil
- Loose or slipping motor coupling so the pump is not turning at speed
Check in this order
- Gauge or stick the tank, then confirm the shutoff valve is open and the vent is clear
- Put a pressure gauge on the pump port, bleed the pump and watch the needle; a fluttering needle means air in the line
- Check the filter and pump screen for sludge or water and replace the filter
- Watch the coupling to see that the pump shaft actually turns with the motor
- If pressure is steady, replace the nozzle with the correct size and spray angle for the unit
- Reset the primary only once or twice; repeated resets flood the chamber with oil
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.