Smoke, soot, odour, pulsation
What is going on
Smoke, soot, a fuel smell in the house and a burner that pulses are all the same story: the oil is not burning cleanly. What I usually find is a bad spray from a worn or dirty nozzle, or a chimney that cannot pull. Soot and odour can also mean combustion byproducts are getting indoors, so treat it seriously.
Likely causes
- Wrong oil pressure at the pump
- Flame hitting the chamber walls
- Not enough draft from a dirty chimney or flue, a stuck or misadjusted draft regulator, or a chamber or heat exchanger leak
- Poor air and oil mixing: worn, loose, dirty or leaking nozzle, closed air shutter, binding fan or tight bearings
Check in this order
- Check the pump pressure with a gauge against the manual
- Look at the flame shape and see if it licks the chamber wall
- Take an overfire and stack draft reading and check the draft regulator moves freely
- Inspect the chimney and flue pipe for soot, blockage or leaks
- Replace the nozzle and confirm it is tight and not weeping
- Open the air shutter as needed and spin the fan by hand to check for binding or tight bearings
- Do a combustion test after the repair and clean the heat exchanger if sooted
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.