Short cycling
What is going on
Nine times out of ten when a gas furnace lights, runs a couple of minutes, shuts off and starts over, it is a plugged filter or a dirty flame sensor. The limit switch trips on heat when the air can't get through, or the board drops the flame because it can't see a steady signal. Short cycling beats up the igniter and blower and wastes gas, so don't just live with it. An oversized furnace or a thermostat sitting right over a supply register can cause the same thing, but rule out airflow and flame first.
Likely causes
- Dirty filter or restricted airflow tripping the limit switch
- Dirty flame sensor or weak flame signal, which is the usual one on a furnace that cycles on flame loss
- Oversized furnace or thermostat placed near a supply register, so the stat is satisfied before the house is
- Thermostat heat anticipator or cycle rate setting wrong for the furnace
- Partially blocked venting or condensate drain causing a pressure switch or drain safety to open
Check in this order
- Replace the filter and check that every supply and return register is open, since closed registers choke the airflow
- Measure temperature rise across the furnace and compare it to the rating plate, high rise means an airflow problem
- Read the control board fault history for limit or flame codes, it usually tells you which way it is dropping out
- Clean the flame sensor with fine abrasive and check flame microamps against the manual
- Watch a full cycle and note whether it quits on limit (burner shuts, blower keeps running) or on flame loss (burner shuts within seconds)
- Check thermostat location and cycle-rate settings, and look for a supply register blowing on the stat
- Inspect venting and the condensate trap for blockage, and call a licensed tech if the vent or gas side needs work
Applies to: Gas furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.