All brands · Furnace troubleshooting
Oil + ignition OK but no flame
What is going on
Oil is flowing, spark is good, still no flame. Usually a spray problem or an air problem. Check the nozzle and pressure first, then draft and air setting. Plugged nozzle is the usual find. Don't keep resetting the primary or you'll just wet the chamber.
Likely causes
- Clogged nozzle or strainer, or a nozzle that is loose in the adapter
- Oil pressure too low
- Oil too heavy or too cold, or the wrong grade
- Too much air or draft blowing the flame off the head
- Electrodes in the wrong spot for the spray
Check in this order
- Pull the nozzle, look at it, replace if dirty or worn
- Gauge the pump pressure and compare it to the nozzle spec in the manual
- Check the nozzle is snug in the adapter
- Check oil grade and tank temperature, especially outdoor tanks in cold weather
- Back off the air band and check overfire draft
- Reset electrode gap and position to the manual
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.