All brands · Furnace troubleshooting
No heat (ignition stage)
What is going on
Generic sequence
Likely causes
- No 120 V/24 V
- Open door interlock
- Open limit/rollout/pressure switch
- Inducer not running
- Pressure switch not closing (blocked vent/condensate)
- Igniter not glowing (cracked/open HSI
- No output from module
- Bad transformer)
- No spark (bad lead
- Gap)
- Gas valve not opening
- Flame not proven (dirty/cracked flame rod
- Grounding
- Polarity)
- Lockout
Check in this order
- Observe how far the start-up sequence gets
- Read board flash code
- Verify 120 V at igniter then at module output
- Ohm the igniter power-off
- Confirm inducer runs and pressure switch closes
- Check limits with meter
- Manometer at manifold
- ΜA flame signal. Service scenarios: no voltage at igniter and none at module output with good igniter resistance → replace module (41A)
- Burners light then drop out, film on flame rod → clean rod (41B)
- Inducer running, pressure switch closed, igniter not glowing, igniter ohms open → replace igniter (41C)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.