Low CO2 (<8 %)

What is going on

A CO2 reading under 8 percent on a combustion test means too much air or too little fuel in the mix. Other readings: high CO2 with smoke points the other way. Read the numbers together with stack temperature and smoke spot.

Likely causes

  • Nozzle too small, so the unit is underfiring
  • Air leaking into the heat exchanger or chamber, diluting the flue gas
  • If CO2 is high with smoke instead: insufficient draft, or overfiring from an oversize nozzle or pump pressure raised too high

Check in this order

  1. Confirm the nozzle size and pump pressure match the nameplate, because wrong nozzle size changes firing rate
  2. Seal air leaks at the burner mount, observation port and heat exchanger joints
  3. Adjust the air band down and retest, watching smoke spot
  4. Take stack temperature and draft readings with each combustion test
  5. If smoke shows, check for low draft and inspect the chimney
  6. Record the final numbers for the next service visit

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.