All brands · Furnace troubleshooting

Indoor blower runs, outdoor unit dead

What is going on

Indoor blower runs but the outdoor unit is dead. The blower running proves you have line voltage and low voltage at the furnace, so I go after what lies between there and the condenser first. In my experience a severed thermostat cable is a common find, especially after a renovation or a rodent. Scenario 32D.

Likely causes

  • Severed thermostat cable
  • Bad transformer
  • Open high-pressure switch
  • Bad thermostat

Check in this order

  1. The running blower proves line and low voltage at the furnace, so start there and move outward
  2. Inspect the low-voltage wiring at the condenser
  3. Check the transformer output and the thermostat
  4. Test the high-pressure switch and find out why it opened, never bypass it
  5. Replace the cable if it is cut or damaged

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.