High stack temperature
What is going on
When I see a high stack temperature on an oil furnace, the first thing I look at is the heat exchanger. A coat of soot acts like insulation, and the heat goes up the chimney instead of into the house. Too much draft or a burner that is firing harder than the rating plate allows will do the same thing and burn through fuel fast.
Likely causes
- Sooted heat exchanger
- Excess draft pulling heat up the flue
- Overfiring, from pressure set too high or an oversize nozzle
Check in this order
- Take a stack temperature and compare it to the manufacturer's target for the unit
- Inspect and clean the heat exchanger and flue passages
- Measure draft at the breech and adjust the draft regulator
- Verify the pump pressure and nozzle size against the nameplate
- Retest after cleaning and tuning, and record the readings
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.