Flame conditions table

What is going on

Read the flame and it tells you how the furnace is burning. A good flame is soft blue, with no yellow tipping, lifting, flashback, pop, float or rollout. Anything else is a combustion problem, and some are dangerous because they make CO. Gas appliance, so a licensed tech does the corrections.

Likely causes

  • Yellow flame, from lack of primary air
  • Lifting flame, from gas velocity faster than burning speed
  • Popping flame, from flashback at shutoff
  • Floating flame, a very dangerous CO condition from incomplete combustion
  • Flame rollout, a very dangerous condition from a blocked flue, poor draft, insufficient air or overfiring

Check in this order

  1. Yellow flame reset primary air and check for blockage.
  2. Lifting flame reduce gas input or primary air.
  3. Popping flame increase gas pressure, reduce primary air, or reduce orifice size. Check the valve and burners.
  4. Floating flame check gas flow, flue, burners, secondary air and primary air. Shut it down until corrected.
  5. Flame rollout check for a blocked flue, poor draft, insufficient air, and overfiring with the same checks.
  6. For any floating or rollout flame, shut the appliance off and test for CO.
  7. Never bypass a rollout or other safety switch.

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.