Cycles on limit (not lockout)
What is going on
The furnace shuts off on the high limit and restarts when it cools down, with no lockout. The burner is heating the exchanger faster than the air can carry the heat away, or the controls are set wrong. Causes and checks are below.
Likely causes
- Thermostat differential or anticipator set too close, giving short cycles
- Limit control set too low
- Overfiring, so the heat exchanger reaches the limit quickly
Check in this order
- Compare the anticipator setting to the control's current draw, because a wrong setting shortens the cycle
- Check the limit setting and cut-out against the rating plate; a low setting trips early
- Verify nozzle size and pump pressure against the nameplate, since overfiring drives temperature up fast
- Check the filter, blower and ductwork for restricted airflow, which also trips the limit
- Run a temperature rise test across the heat exchanger and compare to the nameplate range
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.