Navien · Combi boiler troubleshooting

Hot water not hot enough or too hot - Navien NCB-H

What is going on

Navien NCB-H combi: hot water at the taps is lower or higher than the customer wants. Covers NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H and NCB-190/060H. Check the setpoint, then the piping.

Likely causes

  • DHW set temperature too low or too high
  • Cross-connection between the heating supply and return lines
  • Flow above what the unit can heat for the temperature rise

Check in this order

  1. Check the DHW set temperature. Range is 86-140°F, default 122°F.
  2. Warning: water above 120°F can scald instantly. Warn the customer and use a mixing valve where needed.
  3. Water too cool? Look for a cross-connection between the heating supply and return piping.
  4. Compare the flow with the rated DHW flow at the needed temperature rise for the model.
  5. Test at the tap with a thermometer, not by hand.

Applies to: Navien NCB-H combi boilers: NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB-H User's Information Manual Version 1.0 (April 2024), 5.1 Solving Basic Problems, p.24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.