Navien · Combi boiler troubleshooting

CH series E003 ignition failure - full check

Navien CH ASME

What is going on

The unit tries to light 10 times. No flame after that = E003, manual reset.

Likely causes

  • Gas valve closed or low gas supply / undersized meter or pipe
  • Electrode gap wrong, cracked insulator or arcing to the chamber
  • Ignition transformer or its 120 V feed
  • Main gas valve (no DC power, open coil, stuck solenoid)
  • Dirty or bent flame rod, bad ground
  • APS hose torn or full of water
  • Wrong DIP model setting
  • Gas-air differential out of adjustment
  • Plugged burner nozzle
  • Rainwater in intake / flue
  • Bad PCB

Check in this order

  1. Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Check the gas valve is open. With the boiler at max fire, inlet must be NG 6-10.5 in. W.C. Check dynamic (running) pressure, not just static.
  3. Gas pipe should be 3/4 in. or larger. Overtightened nuts can push the gasket and choke the flow. Check the meter is big enough for all appliances (example in manual: 425 CFH total).
  4. Igniter 97-138 VAC across the two wires of CN17 during ignition. No voltage = PCB.
  5. Pull the electrode. Gap should be about 3-4 mm. Replace if cracked or out of shape. Check spark-wire boots for cracks.
  6. Main gas valve 83-120 VDC on the two brown wires (pins 1-2) of CN15 during ignition. Coil resistance 0.8-2.4 kOhm. You should feel or hear the solenoid click.
  7. Modulating valve 2-10 VDC at CN14.
  8. Flame rod 10-20 VDC at CN19, flame current 7-20 µA (1-20 µA also given). Clean or replace the rod. Check ground: paint under ground screws can break it, and the outlet must be grounded.
  9. Check the APS hose for tears or water left from install.
  10. Check the DIP model setting on the PCB.
  11. Check the gas-air differential at 3-stage min (see gas-air guide).
  12. Quick test cover the blower inlet with your hand during ignition. If it lights, the problem is on the gas supply side.
  13. Pull the manifold and check the nozzles (stage 1 matters most for lighting).
  14. Check the intake for collected rainwater (pipe sloped the wrong way).
  15. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.4 03 Error p.61-68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.