CH series E004 false flame - full check
What is going on
E004 means flame was seen when there should be none: before lighting (standby, pre-purge) or after the gas shut off (post-purge). The fan keeps purging. Auto reset.
Likely causes
- Main gas valve leaking through
- Supply gas pressure too high pushing the valve open
- Spark jumping from electrode to flame rod
- Bad PCB
Check in this order
- Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
- Look through the window. Flame before or after the burn = replace the main gas valve. If gas is leaking, shut the gas off and do not run the unit until repaired.
- Check inlet pressure NG 6-10.5 in. W.C. If it is too high, fix the supply (regulator) and replace the main gas valve.
- Check flame rod position. Spark should not jump to the flame rod. Reposition or replace.
- Check CN19 10-20 VDC, 7-20 µA. Flame signal with burner off = PCB.
- If all checks pass, replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.5 04 Error p.69-70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.