Navien · Combi boiler troubleshooting
CH series breaker trips or remote has no power
What is going on
Symptom guide for CH boilers that trip the breaker at plug-in or while running, or where the room controller is dead.
Likely causes
- Damaged power cord or short
- Transformer or PCB shorted
- Wire pinched after a repair
- Component shorting at a certain stage (e.g. stage 3 gas valve)
- No DC power to the remote terminal
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Trips at plug-in check the cord for damage. Then check the power transformer and the PCB.
- Trips after a repair check every wire you moved. Watch the ignition transformer direction and do not pinch wires under the main gas valve.
- Trips while running note when it happens. Example: trips when stage 3 opens = replace the gas manifold valve.
- Remote dead check 19 VDC or more at the remote terminal. Low = check PCB output and wiring. OK = replace the remote.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 p.111. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.