Navien · Combi boiler troubleshooting

CH series breaker trips or remote has no power

Navien CH ASME

What is going on

Symptom guide for CH boilers that trip the breaker at plug-in or while running, or where the room controller is dead.

Likely causes

  • Damaged power cord or short
  • Transformer or PCB shorted
  • Wire pinched after a repair
  • Component shorting at a certain stage (e.g. stage 3 gas valve)
  • No DC power to the remote terminal

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Trips at plug-in check the cord for damage. Then check the power transformer and the PCB.
  3. Trips after a repair check every wire you moved. Watch the ignition transformer direction and do not pinch wires under the main gas valve.
  4. Trips while running note when it happens. Example: trips when stage 3 opens = replace the gas manifold valve.
  5. Remote dead check 19 VDC or more at the remote terminal. Low = check PCB output and wiring. OK = replace the remote.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 p.111. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.