Navien · Combi boiler troubleshooting
CH series E002 low water pressure / auto fill - full check
What is going on
E002 shows when system pressure is low. The boiler stops and the auto feeder valve tops up. Fill starts at 7.3 psi or less for 4 seconds and stops at about 12 psi (depends on setting). If still under 7.4 psi after 3 minutes, filling stops. The error clears by itself once pressure is back.
Likely causes
- Cold water valve closed or frozen
- Auto feeder valve filter plugged or valve dead
- Water leaking out the condensate hose (left drain valve on main HX open, or leaking HX)
- Leak in heating piping or distributor
- Pressure sensor or display fault
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Open a cold tap to confirm cold supply is on and not frozen.
- Check the auto feeder valve filter for debris.
- Check 97-138 VAC on the auto feeder valve wires (Blue-Blue) when it should fill. Power there and no fill = replace the valve. No power = PCB.
- If water runs out the condensate hose, check the drain valve at the lower left of the main heat exchanger, then check the heat exchanger for leaks.
- Frequent E002 look for leaks at pipe joints and the distributor, and check the expansion tank. Tell the customer (this also leads to E028).
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.3 02 Error p.59-60; 4.6.21 Auto Feeder Valve p.53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.