Navien · Combi boiler troubleshooting

CH series E001 boiling in heat exchanger - full check

Navien CH ASME

What is going on

E001 locks the boiler out when heating water stays at 208°F (98°C) or more for 15 seconds. The pump and fan keep running for post-purge until water drops to 167°F (75°C). Manual reset.

Likely causes

  • Circulation pump not running or weak
  • 3-way valve stuck
  • Heating strainer plugged
  • Main or DHW heat exchanger plugged
  • Heating supply/return or zone valves all closed
  • Supply thermistor reading wrong
  • Wrong capacity DIP setting on PCB
  • Bad PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the pump has 120 VAC while calling. No power at the pump = PCB.
  3. Touch the heating outlet pipe while heating. If it does not warm up, check the 3-way valve: Red+Black 120 VAC = heating, Blue+Black 120 VAC = hot water. Power there but no switch = valve. No power = PCB.
  4. Pull and clean the heating strainer. If it is full of debris, find where it comes from (e.g. corroded distributor).
  5. Make sure the heating supply/return valves are open and at least one zone/distributor valve is always open.
  6. Disconnect the heat exchanger pipes and blow through to check for blockage. If E001 only shows during hot water use, check the DHW heat exchanger.
  7. Compare the displayed supply temp with the real pipe temp. Unplug the thermistor and check 0.8-20 kOhm at CN13. Swap in a known-good sensor if unsure.
  8. Check the PCB DIP switch model/capacity setting.
  9. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.3 01 Error p.56-58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.