CH series E001 boiling in heat exchanger - full check
What is going on
E001 locks the boiler out when heating water stays at 208°F (98°C) or more for 15 seconds. The pump and fan keep running for post-purge until water drops to 167°F (75°C). Manual reset.
Likely causes
- Circulation pump not running or weak
- 3-way valve stuck
- Heating strainer plugged
- Main or DHW heat exchanger plugged
- Heating supply/return or zone valves all closed
- Supply thermistor reading wrong
- Wrong capacity DIP setting on PCB
- Bad PCB
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Check the pump has 120 VAC while calling. No power at the pump = PCB.
- Touch the heating outlet pipe while heating. If it does not warm up, check the 3-way valve: Red+Black 120 VAC = heating, Blue+Black 120 VAC = hot water. Power there but no switch = valve. No power = PCB.
- Pull and clean the heating strainer. If it is full of debris, find where it comes from (e.g. corroded distributor).
- Make sure the heating supply/return valves are open and at least one zone/distributor valve is always open.
- Disconnect the heat exchanger pipes and blow through to check for blockage. If E001 only shows during hot water use, check the DHW heat exchanger.
- Compare the displayed supply temp with the real pipe temp. Unplug the thermistor and check 0.8-20 kOhm at CN13. Swap in a known-good sensor if unsure.
- Check the PCB DIP switch model/capacity setting.
- If all checks pass, replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.3 01 Error p.56-58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.