Navien · Combi boiler troubleshooting

CH series noise problems

Navien CH ASME

What is going on

Symptom guide for CH boilers that are noisy: vibration, regular hum, pops at ignition, whistling or rumble while firing, boiling noise.

Likely causes

  • Unit not level or loose on the wall
  • Fan out of balance
  • 3-way valve micro switch keeps the motor running
  • Gas-air differential set wrong
  • Main gas valve proportional valve faulty
  • Air pressure sensor faulty or APS hose torn
  • Exhaust being pulled into intake
  • Low gas pressure (flame lifting)
  • Dirty nozzles
  • Heat exchanger scaling (boiling noise)

Check in this order

  1. Vibration check the mounting and level. Touch the fan. If it shakes or the noise stops with the case lid off, replace the fan motor.
  2. Constant motor noise 3-way valve micro switch fault. Replace the 3-way valve.
  3. Pop or bang at ignition check the gas-air differential at 3-stage min (DIP 1 and 2 ON). 210/240 standard is 17±1 mm H2O. If noise stays at standard, adjust a little above or below.
  4. Whistle or rumble while firing check inlet gas pressure, nozzles, APS and APS hose (noise can come and go with hose damage).
  5. Compare the flame on stages 1, 2 and 3. An uneven section points to a dirty nozzle.
  6. Check spacing between intake and exhaust and between units.
  7. Boiling noise check raise water to 158°F (70°C) and listen.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.1 Noise p.108. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.