Navien · Combi boiler troubleshooting
CH series no space heat while burner runs / warm floor with heat off
What is going on
Symptom guide for CH boilers that fire but do not heat the zones, short cycle on low flow, or put heat into the floor when heating is off.
Likely causes
- Heating strainer plugged
- Distributor or old piping plugged, or only one zone valve open
- Pump impeller worn or slow
- Supply or return thermistor reading high
- Small DHW leak or pressure changes trigger the 5-minute DHW wait
- 3-way valve not switching or leaking past (heat into floor)
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Clean the heating strainer and find the source of debris.
- Open the distributor valves and balance them. One open zone alone slows heating.
- Check pump output. Replace if the impeller is worn.
- Compare sensor readings with real temps. Replace a thermistor that reads high.
- Unplug the flow sensor and run heat. If it now heats, a small DHW leak or a booster pump on the cold line is making the unit wait in DHW mode.
- Warm floor with heating off the 3-way valve is not closing the heating side. Replace the 3-way valve.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 p.110. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.