Navien · Combi boiler troubleshooting

CH series hot water problems (cold, lukewarm or none)

Navien CH ASME

What is going on

Symptom guide for CH combis with no hot water, low hot water temperature or cold slugs.

Likely causes

  • Hot and cold pipes swapped
  • Flow sensor sticking
  • 3-way valve not switching to DHW
  • Supply thermistor reading high
  • DHW heat exchanger leaking cold into hot
  • Setpoint set low
  • Water pressure/flow too high for the unit
  • Cold water mixing at the fixture or crossover
  • Plugged cold water filter or frozen pipe
  • Debris in internal circulation

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check hot and cold connections are not swapped.
  3. Check the hot water setpoint on the remote.
  4. Flow sensor cleaning can work for now, but replace it. Flow should read 00 with no draw.
  5. 3-way valve if DHW temp does not rise while firing, check the heating outlet pipe. Check 120 VAC Blue+Black at the valve. No power = PCB.
  6. If the remote shows hot water but the tap is cold, suspect the supply thermistor reading high. Replace it.
  7. Burner runs fine but DHW stays low DHW heat exchanger may be mixing cold in. Replace it.
  8. Too much flow for the unit fit a pressure reducing valve. Example in manual: CH-210 gives 4.5 GPM at a 77°F rise.
  9. Hot at the unit but cold at the tap look for crossover or a faulty mixing tap.
  10. Check the cold water valve is open, the cold water filter is clean and pipes are not frozen.
  11. Touch both sides of the DHW heat exchanger. A big difference means it is plugged.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 Hot water p.109. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.