Navien · Combi boiler troubleshooting

CH series gas inlet pressure and gas-air ratio check

Navien CH ASME

What is going on

How to check inlet gas pressure and set the gas-air differential on CH boilers. Licensed gas tech only.

Likely causes

  • Low or high inlet pressure
  • Gas-air differential out of spec after a gas valve or PCB change

Check in this order

  1. Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Inlet shut the gas, run hot water until the unit drops out, then fit a manometer to the inlet test port and zero it.
  3. Open the gas, check for leaks, and open several high-flow taps to reach max fire. Expect NG 6.0-10.5 in. W.C, LP 8.0-13.5 in. W.C.
  4. Gas-air shut the gas, remove the front panel, connect the manometer high side to the GPS tube and low side to the APS tube. Open the gas and leak test.
  5. DIP 1 ON and 2 ON = 3-stage min. Open a hot tap. Adjust the proportional valve to spec.
  6. DIP 1 ON and 2 OFF = 3-stage max. Run high flow. Adjust with the variable resistor on the PCB.
  7. Spec (NG) CH-180 min 0.86 ± 0.04 / max 2.68 ± 0.08 in. W.C. CH-210 min 0.63 ± 0.04 / max 1.61 ± 0.08. CH-240 and CH-240 ASME min 0.63 ± 0.04 / max 2.13 ± 0.08.
  8. Put the DIP switches back to normal, refit the tubes and the panel. Do this check after any PCB swap.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 6.2 Measuring Gas Pressure Setting p.113-115; 8.2.1 p.118. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.