Navien · Combi boiler troubleshooting
CH series E039 water flow sensor (cascade) - full check
What is going on
E039 is a flow sensor fault seen when more than one unit runs in a cascade. The boiler locks out (manual reset).
Likely causes
- No cold water to the unit (frozen or closed valve)
- Flow sensor connector or sensor failed
- Bad PCB
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Take the unit out of the cascade and open a hot tap.
- No water flow check the cold water supply and valves.
- Water flows but still faults check the flow sensor plug, then replace the sensor.
- If all checks pass, replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.26 39 Error p.106. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.