Navien · Combi boiler troubleshooting

CH series E039 water flow sensor (cascade) - full check

Navien CH ASME

What is going on

E039 is a flow sensor fault seen when more than one unit runs in a cascade. The boiler locks out (manual reset).

Likely causes

  • No cold water to the unit (frozen or closed valve)
  • Flow sensor connector or sensor failed
  • Bad PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Take the unit out of the cascade and open a hot tap.
  3. No water flow check the cold water supply and valves.
  4. Water flows but still faults check the flow sensor plug, then replace the sensor.
  5. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.26 39 Error p.106. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.