Navien · Combi boiler troubleshooting

CH series E036 cascade communication - full check

Navien CH ASME

What is going on

E036 shows when the master and slave units in a cascade stop talking.

Likely causes

  • A unit in the cascade has no power
  • Comm cable damaged or unplugged
  • Wrong DIP switch setting
  • Wrong cascade setting

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check every unit in the cascade has power.
  3. Check the communication cable along its length and at both plugs.
  4. Check the DIP switches and cascade settings on each unit.
  5. If it stays, call Navien tech support (manual instruction).

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.25 36 Error p.105. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.