CH series E035 gas pressure sensor (GPS) - full check
What is going on
E035 shows when the GPS output sits at about 0.1 V or 4.5 V for 5 seconds. Manual reset.
Likely causes
- No gas (valve closed, meter problem)
- GPS hose kinked or torn
- Failed GPS
- Bad PCB
Check in this order
- Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
- Check the gas valve is open and the meter is OK. Measure the gas pressure drop at max fire.
- Check the GPS hose for kinks or tears.
- GPS power 5 VDC (red-black). GPS signal: 0.3-4.5 VDC (white-black). The flowchart gives about 0.2-0.6 VDC with the gas valve on and 1-4 VDC with it off at CN7.
- Bad readings = replace the GPS. Good readings and still E035 = PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.24 35 Error p.103-104; 4.6.12 GPS p.43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.