Navien · Combi boiler troubleshooting

CH series E035 gas pressure sensor (GPS) - full check

Navien CH ASME

What is going on

E035 shows when the GPS output sits at about 0.1 V or 4.5 V for 5 seconds. Manual reset.

Likely causes

  • No gas (valve closed, meter problem)
  • GPS hose kinked or torn
  • Failed GPS
  • Bad PCB

Check in this order

  1. Gas work licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Check the gas valve is open and the meter is OK. Measure the gas pressure drop at max fire.
  3. Check the GPS hose for kinks or tears.
  4. GPS power 5 VDC (red-black). GPS signal: 0.3-4.5 VDC (white-black). The flowchart gives about 0.2-0.6 VDC with the gas valve on and 1-4 VDC with it off at CN7.
  5. Bad readings = replace the GPS. Good readings and still E035 = PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.24 35 Error p.103-104; 4.6.12 GPS p.43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.