Navien · Combi boiler troubleshooting

CH series E030 exhaust high limit - full check

Navien CH ASME

What is going on

E030 shows when the exhaust limit switch at the top of the exhaust duct opens for 1 second. It opens at 149°F (65°C). The boiler locks out and post-purges. The code clears by itself once the switch closes.

Likely causes

  • Exhaust running hot (scaled or dirty heat exchanger)
  • Exhaust limit switch failed
  • Bad PCB

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Let it cool, then pull the switch and check it with a meter. Very high resistance (MOhm) when cool = bad switch.
  3. The code table says to clean the inlet water filter and flush the heat exchanger if it trips from heat.
  4. If the switch is good, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.23 30 Error p.102; 5.1 p.55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.