Navien · Combi boiler troubleshooting

CH series E028 water leak / repeated low pressure - full check

Navien CH ASME

What is going on

E028 shows if heating pressure stays at 7.3 psi or less for 5 minutes, or drops to 7.3 psi again within 2 hours after an auto fill. It is held off for the first 72 hours after first power-up. Manual reset.

Likely causes

  • Leak inside the boiler or in the heat exchanger
  • Leak in system piping
  • Auto feeder valve plugged or dead
  • Pressure sensor fault
  • Cold water supply off or frozen

Check in this order

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Look for leaks inside the unit and on the system piping.
  3. Heat exchanger leak test set trial mode (DIP 2-2 ON). If water keeps running out the condensate hose, the heat exchanger is leaking.
  4. Auto feeder valve clean its filter. Drain some water from the pump drain and see if it refills.
  5. Check 120 VAC at CN21 pins 1 and 3 when filling. Power and no fill = replace the valve. No power = PCB.
  6. Press reset fill should finish within 5 minutes.
  7. Check the cold water supply is open and not frozen.
  8. If all checks pass, replace the PCB.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.22 28 Error p.100-101. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.