Navien · Combi boiler troubleshooting
CH series E028 water leak / repeated low pressure - full check
What is going on
E028 shows if heating pressure stays at 7.3 psi or less for 5 minutes, or drops to 7.3 psi again within 2 hours after an auto fill. It is held off for the first 72 hours after first power-up. Manual reset.
Likely causes
- Leak inside the boiler or in the heat exchanger
- Leak in system piping
- Auto feeder valve plugged or dead
- Pressure sensor fault
- Cold water supply off or frozen
Check in this order
- Turn off power before unplugging connectors or measuring resistance.
- Look for leaks inside the unit and on the system piping.
- Heat exchanger leak test set trial mode (DIP 2-2 ON). If water keeps running out the condensate hose, the heat exchanger is leaking.
- Auto feeder valve clean its filter. Drain some water from the pump drain and see if it refills.
- Check 120 VAC at CN21 pins 1 and 3 when filling. Power and no fill = replace the valve. No power = PCB.
- Press reset fill should finish within 5 minutes.
- Check the cold water supply is open and not frozen.
- If all checks pass, replace the PCB.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.22 28 Error p.100-101. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.